NivoRadar® - NR3000

Sold By :

rjc.co.th



HousingStainless steel 1.4404 (316L), IP68
CertificatesCE, ATEX, CSA, FM
Process Temperature Range-40°C to +200°C
Pressure Range+3bar max.
Supply Voltage24V DC (max. 30V DC) up to max. 550Ohm loop resistance.
Measuring Range40m/100m
Lens MaterialPEI (40m)/PEEK (100m)
Signal Output4 .. 20mA, 2-Wire
CommunicationHART, Profibus PA and via Foundation Fieldbus
Measuring ConditionsDK >1,6
Process ConnectionFlat flange 3"/80mm, 4"/100mm, 6"/150mm in stainless steel 1.4301 (304), 1.4404 (316L) or with adjustable fitting in coated aluminium.
ProgrammingVia display and programming buttons, hand programmer and infrared interface or via HART interface and FDT/Simatic PDM
  • Narrow 4° beam for long measurement ranges and tall, narrow silos.
  • High sensitivity via high reflection from the product.
  • Easy commissioning via quickstart menu.
  • Easy operation and diagnostic via the Local Display Interface (LDI). 
  • Process temperature up to 200°C.
  • Flushed flange mounted lens antenna with integrated air purging system.  
  • Built in aiming flange for optimal alignment of the sensor.