Housing | Aluminium IP66, NEMA Type 4/4X |
Certificates | ATEX, IEC-Ex, FM, CSA, INMETRO, EHEDG; ; also GasEx certification with flameproof housing selected |
Functional Safety | SIL 2 |
Process Temperature Range | -40°C tos +600°C |
Pressure Range | -0,9bar to +10bar |
Sensitivity | min. 15g/l - adjustable in 3 Settings |
Process Connection | G1¼" and G1½"; NPT 1¼" und NPT1½"; Triclamp 2"; flange DN100 PN16, other flanges available |
Process Connection Material | Aluminium or stainless steel 1.4305 (303), 1.4301 (304), 1.4541 (321L) or 1.4404 (316L) |
Measuring Vane / Shaft Material | Aluminium or stainless steel 1.4301 (SS304),1.4305 (303) or 1.4404 (316L) |
Bearing / Seal | Dust-proof ball-bearing, optional in optional in stainless steel or radial shaft seal in in NBR rubber, FPM or PTFE |
Supply Voltage | AC: 24V / 48V/ 115V/ 230V (50-60Hz); DC: 24V; Universal Voltage 24V DC / 22...230V AC |
Signal Output | Microswitch, relay SPDT contact; Relay DPDT contact |
Switchable Signal Output | FSH / FSL with Universal Voltage electronics integrated; with AC Electronics as available option |
Signal Delay | With Universal Electronics is an integrated adjustable time delay of the signal Output. |
Fail Safe Alarm | Optional für Universal Voltage; Monitoring of motor / transmission / electronics / power |
•Suitable for most bulk solids.
•Simple, reliable and maintenance-free measuring principle.
•Insensitive to dust, electrostatic charging and caking.
•Housing available in explosion proof version.
•International approvals for application in hazardous areas (gas and dust).
•Rotatable electronic housing for easy installation.
•Mechanically very stable shaft bearing with ballbearing.
•Process seal with radial shaft seal.
•Rugged die-cast aluminium housing IP66.
•A variety of available process connections and terminal voltages.
•RoHS Compliant.